+91 73596 19429

dprotecta@dbrothers.com

  • Home
  • /
  • Double compression Medium Duty Cable Glands

Technical Specifications

Property Specification
Material Brass
Plating Nickel Plated
Entry Threads BSC Standard (Metric also available)
Sealing Rubber Ring Natural

Applications

Used in normal climatic condition for armored & unarmored cables.

Suitable Cable
Overall Dia From (mm)
Suitable Cable
Overall Dia To (mm)
Size (mm) Size (Inches) D1
Nipple Entry (Inches)
B
length (mm)
C (A/F) (mm) D (A/C) (mm) E Dai. (mm) F Dai. (mm)
6.0 9.0 10 3/8″ 5/8″ 25.0 20.5 23.5 10.0 7.0
9.0 12.0 12 1/2″ 5/8″ 25.0 22.5 26.0 16.5 11.0
12.0 16.0 16 5/8″ 3/4″ 25.0 22.5 26.0 16.5 14.0
16.0 18.0 19 3/4″ 3/4″ 25.0 25.5 29.5 19.0 15.0
18.0 20.0 22 7/8″ 3/4″ 25.0 28.0 32.0 20.0 15.0
20.0 23.0 25 1″ 1″ 25.0 31.0 35.5 23.5 20.0
23.0 26.0 28 1 1/8″ 1 1/8″ 25.0 35.5 41.0 27.0 23.0
26.0 30.0 32 1 1/4″ 1 1/4″ 25.0 41.0 47.0 32.0 25.5
30.0 33.0 35 1 3/8″ 1 3/8″ 25.0 44.0 50.5 35.0 30.0
33.0 37.0 38 1 1/2″ 1 1/2″ 25.0 47.0 54.0 38.0 31.5
37.0 43.0 45 1 3/4″ 1 3/4″ 25.0 57.0 65.5 47.0 43.0
43.0 48.0 50 2″ 2″ 25.0 59.0 68.0 51.0 43.0
48.0 54.0 57 2 1/4″ 2 1/4″ 25.0 66.0 75.0 57.0 50.0
54.0 61.0 63 2 1/2″ 2 1/2″ 25.0 77.0 89.0 65.0 57.0
61.0 67.0 70 2 3/4″ 2 3/4″ 25.0 82.0 95.0 72.0 63.0
67.0 73.0 75 3″ 3″ 25.0 90.0 105.0 75.0 65.0
73.0 78.0 82 3 1/4″ 3 1/4″ 25.0 94.0 108.0 83.0 74.5
78.0 84.0 88 3 1/2″ 3 1/2″ 25.0 103.0 119.0 91.0 79.0
84.0 94.0 100 4″ 4″ 25.0 113.0 130.0 98.0 91.0